datasheetbank_Logo
búsqueda de Hoja de datos y gratuito Fichas de descarga

HAL600-S Ver la hoja de datos (PDF) - LEM Industrial

Número de pieza
componentes Descripción
Lista de partido
HAL600-S Datasheet PDF : 2 Pages
1 2
Current Transducer HAL 50..600-S
For the electronic measurement of DC, AC and pulsed currents,
with a galvanic isolation between the primary (high power) circuit
and the secondary (electronic) circuit.
IPN = 50 A
Electrical data
Primary nominal
r.m.s. current
IPN (A)
Primary current
measuring range
IP (A)
50
± 150
100
± 300
200
± 600
300
± 900
400
± 1000
500
± 1000
600
± 1000
Type
HAL 50-S
HAL 100-S
HAL 200-S
HAL 300-S
HAL 400-S
HAL 500-S
HAL 600-S
ÎP
Overload capacity (Ampere Turns)
VOUT Analogue output voltage @ ± IPN
RL
Load resistance TA = 0 .. + 70°C
TA = - 25 .. + 85°C
VC Supply voltage (± 5 %)
I
Current consumption (max)
C
Vb
Rms rated voltage1)
Vd
Rms voltage for AC isolation test, 50 Hz, 1 mn
Ris
Isolation resistance @ 500 VDC
Accuracy - Dynamic performance data
X
Accuracy 2) @ IPN, TA = 25°C, @ ± 15 V
eL
Linearity 2)
V
OE
VOM
VOT
e TC G
tr
di/dt
f
Electrical offset voltage @ I = 0, T = 25°C
P
A
Residual offset voltage @ IP = 0
after an overload of 3 x IPN
Thermal drift of offset voltage TA = - 25 .. + 85°C
Thermal drift of gain TA = - 25 .. + 85°C
Response time @ 90 % of IP
di/dt accurately followed
Frequency bandwidth (- 3 dB) 3)
30000
A
±4
V
>1
kW
>3
kW
± 15
V
25
mA
500
V
3
kV
> 500
MW
±1
%
± 0.5
%
Max
± 10
mV
± 10
±2
± 0.05
<3
> 50
DC .. 50
mV
mV/°K
%/°K
µs
A/µs
kHz
General data
TA
Ambient operating temperature
T
Ambient storage temperature
S
m Mass
Standards Safety
EMC
Deviation in output when tested to EN 61000-4-6
Deviation in output when tested to EN 61000-4-4
- 25 .. + 85
°C
- 25 .. + 85
°C
75
g
EN50178 (1994)
EN50082-2 (1992)
EN50081-1 (1992)
< 10
< 10
% of IPN
% of I
PN
Notes : 1) Overvoltage Category III, Pollution Degree 2
2) Excludes the electrical offset
3) Refer to derating curves in the technical file to avoid excessive core
heating at high frequency
LEM Components
Features
· Open loop transducer using Hall
Effect
· Panel mounting - Horizontal or
Vertical
· Insulated plastic case to UL 94-V0.
Advantages
· Very good linearity
· Very good accuracy
· Low temperature drift
· Wide frequency bandwidth
· Very low insertion losses
· High immunity to external
interference
· Current overload capability
· Low power consumption
· Wide dynamic range, 50 to 600 A in
one package.
Applications
· AC variable speed drives and servo
motor drives
· Static converters for DC motor drives
· Battery supplied applications
· Uninterruptable Power Supplies
(UPS)
· Switched Mode Power Supplies
(SMPS)
· Power supplies for welding
applications.
001107/1
www.lem.com

Share Link: 

datasheetbank.com [ Privacy Policy ] [ Request Datasheet ] [ Contact Us ]