Voltage Transducer AV100 Series
For the electronic measurement of voltages : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high voltage)
and the secondary circuit (electronic circuit).
VPN = 50...1500 V
Electrical data
Primary nominal
Primary Voltage R.m.s. voltage for AC Type
R.m.s or DC voltage measuring range isolation test1)
VPN (V)
50
VPmax (V)
± 75
(50 Hz/1min)
Vd (kV)
3.3
AV 100-50
125
± 187.5
3.3
AV 100-125
150
± 225
3.3
AV 100-150
250
± 375
3.3
AV 100-250
500
± 750
3.3
AV 100-500
750
± 1125
4.3
AV 100-750
1000
± 1500
5.5
AV 100-1000
1500
± 2250
6.5
Vˆ P Not measurable overload
2 x VPmax (1s/h)
RM Measuring resistance
@ VC=11.4V
@ VC=22.8V
ISN Secondary nominal r.m.s. current
VC Supply voltage (± 5 %)
Ic
Current consumption
Max Common mode voltage
and
Ve
R.m.s. voltage for partial discharge
extinction @ 10pC
AV 100-1500
RM min
0
VDC
RM max
47
0
184
50
mA
DC ± 12 .. 24 V
50+IS
mA
U HT+ + UHT- ≤ 4.2 k V DC
UHT+ - UHT-≤ VPMAX
1.1 2)
kV
2.2 3)
kV
Accuracy - Dynamic performance data
X G Overall Accuracy @ VPN , TA = + 25°C
X G Overall Accuracy @ VPN , TA = - 25 .. + 70°C
εX G
L
Overall Accuracy @ VPN , TA = - 40 .. + 85°C
Linearity @ TA = 25°C
IO
Offset current @ VP = 0, TA = 25°C
tr
Response time @ 10 % of VPmax
f
Frequency bandwidth (- 3 dB)
± 0.7
%
± 1.5
%
± 1.7
%
< 0.1
%
± 0.15
mA
Between 10 and 13 µs
DC .. 13
kHz
General data
TA
Ambient operating temperature
TS
Ambient storage temperature
m Mass
Standards
- 40 .. + 85
°C
- 50 .. + 90
°C
375
g
EN 50155
EN 50124-1
NFF16101/2
Features
Insulated plastic case recognized
according to UL 94-V0.
Included primary resistor
Advantages
Low power
Excellent accuracy
Very good linearity
Low thermal drift
Low response time
High bandwidth
High immunity to external
interference
Low disturbance in common mode.
Applications
AC variable speed drives and servo
motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies
(UPS)
Power supplies for welding
applications .
Notes : 1) Between primary and secondary
2) For models AV 100-50 to 750
3) For models AV 100-1000 & AV 100-1500
030523/4