E5AX-P
E5AX-P
Characteristics
Setting accuracy
Indication accuracy
Disable band
Proportional band
Integral time
Derivative time
Alarm output setting range
Alarm output hysteresis
Sampling period
Output refresh period
Display refresh period
Valve travel indication
Full Open/close time
Input shift
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Life expectancy
Ambient temperature
Ambient humidity
Memory protection
Enclosure ratings
(+0.3% of set value or +1%C, whichever greater), +1 digit max.
(+0.3% of set value or +1%C, whichever greater), +1 digit max. (Set value coincides with the
indicated value, because no relative error exists between both values.)
0.1% to 10.0% (in units of 0.1%)
0.1% to 999.9 %C/%F (in units of 0.1%C/%F)
1 to 3,999 s (in units of 1 s)
0 to 3,999 s (in units of 1 s)
Thermocouple: –999% to 9,999%C/%F (in units of 1%C/%F)
Platinum resistance thermometer: –99.9% to 999.9%C/%F (in units of 0.1%C/%F)
0.0% to 999.9 %C/%F (in units of 0.1%C/%F)
500 ms (temperature sensor input)
500 ms
500 ms (temperature sensor input)
–99% to 999% (in units of 1%)
1 to 999 s ( in units of 1 s)
Thermocouple: –999% to 9,999%C/%F (in units of 1%C/%F)
Platinum resistance thermometer: –99.9% to 999.9%C/%F (in units of 0.1%C/%F)
20 MW min. (at 500 VDC)
2,000 VAC 50/60 Hz for 1 min between terminals of different polarities
Malfunction: 2 to 55 Hz, 2G 10 min each in X, Y, and Z directions
Destruction: 10 to 55 Hz, 0.75-mm double amplitude 2 hrs each in X, Y, and Z directions
Malfunction: 200 m/s2 3 times each in 6 directions
Destruction: 300 m/s2 3 times each in 6 directions
Mechanical: 10,000,000 operations min.
Electrical: 100,000 operations min.
Operating: –10% to 55%C (with no icing)
Storage: –25% to 65%C (with no icing)
Operating: 35% to 85%
Non-volatile memory
Front panel: IEC standard IP50
Rear case: IEC standard IP20
Terminals: IEC standard IP00
Weight
Standard: Approx. 350 g; Communications: Approx. 480 g; Mounting bracket: Approx. 50 g
*The accuracy of U thermocouples under temperatures from –150% to 400%C (–240% to 700%F) is +2%C (+3.6%F) +1 digit. Accuracy is
reduced below –150%C (–240%F). The accuracy of R and S thermocouples under 0% to 200%C (0% to 400%F) is +3%C (+5.4%F) +1 digit.
3