datasheetbank_Logo
búsqueda de Hoja de datos y gratuito Fichas de descarga

LA55-TP Ver la hoja de datos (PDF) - LEM Industrial

Número de pieza
componentes Descripción
Lista de partido
LA55-TP
LEM
LEM Industrial LEM
LA55-TP Datasheet PDF : 3 Pages
1 2 3
Current Transducer LA 55-TP
For the electronic measurement of currents : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
IPN = 50 A
Electrical data
16016
IPN
Primary nominal r.m.s. current
IP
Primary current, measuring range
RM Measuring resistance @
with ± 12 V
with ± 15 V
@ ± 50 A max
@ ± 70 A
max
@ ± 50 A max
@ ± 70 A
max
I
Secondary nominal r.m.s. current
SN
K N Conversion ratio
V
Supply voltage (± 5 %)
C
IC
Current consumption
50
A
0 .. ± 70
A
TA = 70°C TA = 85°C
RM min RMmax RM min RMmax
10 100 60 95
10 50 60 1) 60 1)
50 160 135 155
50 90 135 2)135 2)
50
mA
1 : 1000
± 12 .. 15
V
10 (@ ± 15 V) + IS mA
Accuracy - Dynamic performance data
X
Accuracy @ IPN , TA = 25°C
@ ± 15 V (± 5 %) ± 0.65
%
@ ± 12 .. 15 V (± 5 %) ± 0.90
%
εL
Linearity error
< 0.15
%
Typ Max
I
Offset current @ I = 0, T = 25°C
O
P
A
± 0.2 mA
IOM
Residual current 3) @ IP = 0, after an overload of 3 x IPN
± 0.3 mA
I
Thermal drift of I
OT
O
0°C .. + 70°C ± 0.1 ± 0.5 mA
- 25°C .. + 85°C ± 0.1 ± 0.6 mA
tra
tr
di/dt
f
Reaction time @ 10 % of IP max
Response time 4) @ 90 % of IP max
di/dt accurately followed
Frequency bandwidth @ 30A (- 3 dB)
General data
< 500
< 2.5
> 200
DC .. 100
ns
µs
A /µ s
kHz
TA
Ambient operating temperature
T
Ambient storage temperature
S
R S Secondary coil resistance @
m
Mass
Standards
TA = 70°C
T = 85°C
A
- 25 .. + 85
°C
- 40 .. + 90
°C
80
85
24
g
EN 50178 : 1997
Features
Closed loop (compensated) current
transducer using the Hall effect
Printed circuit board mounting
Insulated plastic case recognized
according to UL 94-V0.
Advantages
Excellent accuracy
Very good linearity
Low temperature drift
Optimized response time
Wide frequency bandwidth
No insertion losses
High immunity to external
interference
Current overload capability.
Applications
AC variable speed drives and servo
motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies
(UPS)
Switched Mode Power Supplies
(SMPS)
Power supplies for welding
applications.
Application Domain
Industrial
Notes : 1) Measuring range limited to ± 60 A
max
2) Measuring range limited to ± 55 A max
3) Result of the coercive field of the magnetic circuit
4) With a di/dt of 100 A/µs.
LEM
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
060126/7
Page 1/3
w w w .lem.com

Share Link: 

datasheetbank.com [ Privacy Policy ] [ Request Datasheet ] [ Contact Us ]