Current Transducer LTC 600-S
For the electronic measurement of currents : DC, AC, pulsed...,
with a galvanic isolation between the primary circuit (high power)
and the secondary circuit (electronic circuit).
IPN = 500 A
Electrical data
IPN
Primary nominal r.m.s. current
I
Primary current, measuring range @ 24 V
P
ÎP
Max overload not measurable
RM Measuring resistance
with ± 15 V
with ± 24 V
@ ± 500 A max
@ ± 1200 A
max
@ ± 500 A max
@ ± 1500 A
max
ISN
Secondary nominal r.m.s. current
K
Conversion ratio
N
VC Supply voltage (± 5 %)
I
Current consumption
C
Accuracy - Dynamic performance data
X G Overall accuracy @ IPN , TA = 25°C
εL
Linearity
@ I , T = - 40°C .. + 85°C
PN A
IO
IOT
tr
di/dt
f
Offset current @ IP = 0, TA = 25°C
Thermal drift of IO
Response time 1) @ 90 % of IPN
di/dt accurately followed
Frequency bandwidth (- 1 dB)
- 40°C .. + 85°C
General data
TA
Ambient operating temperature
T
Ambient storage temperature
S
R S Secondary coil resistance @ TA = 85°C
m
Mass
Standards
500
A
0 .. ± 1500
A
10 / 10 kA/ms
R R M min
M max
0
70
0
5
0
150
0
20
100
mA
1 : 5000
± 15 .. 24
V
<
30
(@ ± 24 V) +
I
S
mA
< ± 0.7
< ± 1.6
< 0.1
Max
± 0.5
±1
<1
> 100
DC .. 100
%
%
%
mA
mA
µs
A/µ s
kHz
- 40 .. + 85
°C
- 45 .. + 90
°C
44
750
g
EN 50155 : 2001
Features
Closed loop (compensated) current
transducer using the Hall effect
Insulated plastic case recognized
according to UL 94-V0
Railway equipment.
Advantages
Excellent accuracy
Very good linearity
Low temperature drift
Optimized response time
Wide frequency bandwidth
No insertion losses
High immunity to external
interference
Current overload capability.
Applications
AC variable speed drives and servo
motor drives
Static converters for DC motor drives
Battery supplied applications
Uninterruptible Power Supplies
(UPS)
Switched Mode Power Supplies
(SMPS)
Power supplies for welding
applications.
Application Domain
Traction
Note: 1) With a di/dt of 100 A/µs.