DEVICE CHARACTERISTICS
TEL185B
&
TEL185E
MAXIMUM RATINGS @ 25°C
Peak Operatiing Line Voltage (VOP)
Operating Line Current (I )
O
Maximum Transient Voltage
Maximum Transient Current
(8/20µs waveform)
Operating & Storage Temperature
Response Time
±185VPEAK
200mA
20kV
10kA/Wire
40kA/Protector
-55°C to 100°C
< 1 nanosecond
ELECTRICAL CHARACTERISTICS @ 25°C
MAXIMUM
CLAMPING
VOLTAGE
(8/20µs)
@ ±500A
VC
VOLTS
MAXIMUM LINE
THRUPUT
RESISTANCE
R
OHMS
MAXIMUM
LEAKAGE
CURRENT
@ ±185VOP
ID
µA
MAXIMUM
CAPACITANCE
@ 0V, 1MHz
C
pF
330
12
5
800
INSTALLATION INSTRUCTIONS
There are five (5) terminals on both the line and equipment side of the
TEL185E - four telcom line terminals and one ground terminal. The
ground terminal, as shown on the label, is connected internally. A single
ground connection is sufficient. However, it is recommended that both
ground connections be used for a lower impedance path to earth. This
connection can be made through the green AC power ground wire or a
known earth ground. The ground wire should be #14 stranded wire.
Incoming telcom lines are cut or disconnected from the equipment to
insert the TEL185E product. The line side of the terminals are to be
connected to outside telephone or telecommunication lines that carry the
transient threats into the equipment to be protected. The equipment
side of the terminals are to be connected to the equipment to be
protected. The location of the product should be such that these wires
are as short as possible. A #18 or 20 gauge wire can be used for these
connections.
The TEL185B requires an edge connector interface for installation. A
standard 15 position edge connector can be used. When mounting or
wiring the connectors onto a printed circuit board, be sure that the
correct terminals are soldered. The line side of the board connections
are finger contacts 2 thru 5. The boards are conformal coated for limited
protection against moisture.
ProTek’s telcom line protector is designed with a short circuit failure mode
to give maximum protection. A fuse, PTC, fussable link, or circuit breaker
is recommended for each signal line on the input (line) side of the
protector for those applications that require an open circuit failure mode.
Caution: A low DC resistance ground may not be indicative of a good
lightning ground. Lightning contains a broad spectrum of frequencies -
up to 1 MHz. A low impedance path to ground at the transient frequen-
cies is necessary. A ground strap is recommended or a #6 AWG
stranded wire. For wire lengths over 1.5 meters, there may be some
excessive line to earth potential under severe thunderstorm conditions.
For these applications, an additional protector may be necessary at the
equipment interface.
05050.R3 11/03
2
www.protekdevices.com