E5AN-H/E5EN-H
Alarm Outputs
Each alarm can be independently set to one of the following 13 alarm types. The default is 2: Upper limit.
Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified.
Note: For models with heater burnout, SSR failure, and heater overcurrent detection, alarm 1 will be an OR output of the alarm selected from the
following alarm types and the alarms for heater burnout, SSR failure, and heater overcurrent. To output only a heater burnout alarm, SSR
failure alarm, and heater overcurrent alarm for alarm 1, set the alarm type to 0 (i.e., no alarm function).
Set value
Alarm type
Alarm output operation
When alarm value When alarm value
X is positive
X is negative
Description of function
0
Alarm function OFF
Output OFF
No alarm
1
Upper- and lower-limit *1
ON
OFF
LH
*2
SP
Set the deviation in the set point by setting the alarm
upper limit (H) and alarm lower limit (L).
2
Upper-limit
ON
OFF
X
SP
ON
X
OFF
SP
Set the upward deviation in the set point by setting
the alarm value (X).
3
Lower-limit
ON
X
OFF
SP
ON
OFF
X
SP
Set the downward deviation in the set point by setting
the alarm value (X).
4
Upper- and lower-limit range *1
ON
OFF
LH
*3
SP
Set the deviation in the set point by setting the alarm
upper limit (H) and alarm lower limit (L).
5
Upper- and lower-limit with
standby sequence *1
ON
LH
OFF
SP
*4
*5
A standby sequence is added to the upper- and
lower-limit alarm (1). *7
6
Upper-limit with standby sequence
ON
OFF
X
SP
ON
X
OFF
SP
A standby sequence is added to the upper-limit alarm
(2). *7
7
Lower-limit with standby sequence
ON
OFF
X
SP
ON
OFF
X
SP
A standby sequence is added to the lower-limit alarm
(3). *7
8
Absolute-value upper-limit
ON
OFF
X
0
ON
X
The alarm will turn ON if the process value is larger
OFF
0
than the alarm value (X) regardless of the set point.
9
Absolute-value lower-limit
ON
OFF
X
0
ON
X
The alarm will turn ON if the process value is smaller
OFF
0
than the alarm value (X) regardless of the set point.
10
Absolute-value upper-limit with
standby sequence
ON
OFF
X
0
ON
X
A standby sequence is added to the absolute-value
OFF
0
upper-limit alarm (8). *7
11
Absolute-value lower-limit with
standby sequence
ON
OFF
X
0
ON
X
A standby sequence is added to the absolute-value
OFF
0
lower-limit alarm (9). *7
12
LBA (alarm 1 type only)
---
*8
13
PV change rate alarm
---
*9
14
RSP absolute value upper limit *6
ON
OFF
X
0
ON
X
OFF
The alarm turns ON when the remote SP (RSP) is
larger than the alarm value (X). This alarm functions
0
in both Local SP and Remote SP Modes.
15
RSP absolute value lower limit *6
ON
OFF
X
0
ON
X
OFF
The alarm turns ON when the remote SP (RSP) is
smaller than the alarm value (X). This alarm
0
functions in both Local SP and Remote SP Modes.
*1. With set values 1, 4 and 5, the upper and lower limit values can
be set independently for each alarm type, and are expressed as
“L” and “H.”
*2. Set value: 1, Upper- and lower-limit alarm
Case 1
Case 2
Case 3 (Always ON)
L H SP
H < 0, L > 0
H< L
SP L H
H > 0, L < 0
H> L
H SP L
H L SP
SP H L
*3. Set value: 4, Upper- and lower-limit range
H < 0, L < 0
H < 0, L > 0
H⏐ ≥ ⏐L
H > 0, L < 0
H⏐ ≤ ⏐L
Case 1
Case 2
Case 3 (Always ON)
H < 0, L < 0
L H SP
SP L H
H SP L
H < 0, L > 0
H< L
H > 0, L < 0
H> L
H L SP
H < 0, L > 0
H⏐ ≥ ⏐L
H > 0, L < 0
SP H L
H⏐ ≤ ⏐L
*4. Set value: 5, Upper- and lower-limit with standby sequence
For Upper- and Lower-Limit Alarm Described Above
Case 1 and 2
Always OFF when the upper-limit and lower-limit hysteresis
overlaps.
Case 3: Always OFF
*5. Set value: 5, Upper- and lower-limit with standby sequence
Always OFF when the upper-limit and lower-limit hysteresis
overlaps.
*6. Displayed when there is a remote SP input.
*7. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature
Controllers User's Manual Basic Type (Cat. No. H156) for
information on the operation of the standby sequence.
*8. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature
Controllers User's Manual Basic Type (Cat. No. H156) for
information on the loop burnout alarm (LBA).
*9. Refer to the E5CN/E5AN/E5EN/E5GN Digital Temperature
Controllers User's Manual Basic Type (Cat. No. H156) for
information on the PV change rate alarm.
7